3-13
Cisco MGX 8800/8900 Series Hardware Installation Guide
Releases 2 - 5.2, Part Number OL-4545-01, Rev. H0, May 2006
Chapter3 Preparing for Installation
Site Requirements for the MGX 8850 or MGX 8850/B Switch
Space
You can install the following MGX 8850 or MGX 8850/B system components in a rack (as shown in
Figure 3-3):
Exhaust plenum
Upper fan tray
Cisco MGX 8850 switch
Lower fan tray
Air intake plenum
AC power supply tray (optional)
Non-Operational None. 1.12 Grms, 3 to 500 Hz
Spectral break points of
0.0065 G1/Hz at 10 Hz and 100 Hz
5 dB/octave roll-off at each end
30 minutes in each of 3 axes
Earthquake No damage to the switch when tested
to earthquake waveform.
75-mm maximum single amplitude
deflection.
Frame-level natural mechanical
resonant frequency > 2 Hz.
Frame-level natural mechanical
resonant frequency > 6 Hz.
Product must function before and
after vibration is applied to each axis
(x = side to side, y = front to back, z
= up and down).
Product must operate without loss of
service during earthquake testing.
None
1. Office product—More than 2 m from regularly inhabited positions
2. Cisco package test specification
Table3-2 Vibration Condition Recommendations (continued)
Category NEBS Description MDVT Description