Cisco MGX 8800/8900 Series Hardware Installation Guide
Releases 2 - 5.2, Part Number OL-4545-01, Rev. H0, May 2006
Appendix
Control and Clock Cabling
FigureB-2 Optional RJ-45 to Wire-wrap
Note The eight pins of the adapter are marked and have a one-t o-one correlation to the eight lines on the RJ-45
connector.
When you install the RJ-45 to wire-wrap adapter, you do not need to remove the card from its slot or
turn off the power. However, you should wire-wrap the cable conductors to the applicable pins on the
adapter before you plug the adapter into the card .
Complete the following steps to connect the external clock using the wire-wrap adapter:
Step1 Remove the pin cover from the adapter (see Figure B-3). The pin cover provides ESD shielding.
FigureB-3 Removing the Pin Cover from the Adapter
Step2 Insert the shielded clock source cable through the hole of the pin cover. See Figure B-4.
Note You must use ashielded clock source cable to ensur e EMI containment.
FigureB-4 Inserting the Cable through the Pin Cover
Note The length of the exposed (unshielded) wires should be 2 to 4 inches. The maximum allowable
length is 4 inches.