Cisco Systems OL-20932-02 manual CAN Bus Connections for Optional Modules, Related Documentation

Models: OL-20932-02

1 94
Download 94 pages 10.95 Kb
Page 15
Image 15
CAN Bus Connections for Optional Modules

Chapter 1 Overview

Optional Expansion Modules

CAN Bus Connections for Optional Modules

The optional modules are connected to a Cisco Physical Access Gateway using a CAN bus connection, as shown in Figure 1-5.

Figure 1-5

CAN Bus Wiring

CAN+

Sheild

CAN-

Gateway Module

Reader Module

Input Module

Output Module

271589

The CAN bus must adhere to the following rules:

The maximum length for the CAN bus is 1320 feet (400 Metres).

The last device in a CAN bus must be terminated by setting the CAN terminator switch to ON.

The CAN terminator switch in included on the Reader, Input and Output modules only (the Gateway is always the first device in the CAN bus).

Set the terminator switch to OFF for all other modules in the CAN bus.

For the location of the CAN terminator on each device, see the physical port description for that device.

The Gateway and Reader modules are connected using the CAN1 interface. The CAN2 interface is not supported in this release.

Related Documentation

See the following chapters for instructions to install the modules and related equipment:

Chapter 2, “Installing and Configuring the Cisco Physical Access Gateway”

Chapter 3, “Connecting a Cisco Reader Module”

Chapter 4, “Connecting a Cisco Input Module”

Chapter 5, “Connecting a Cisco Output Module”

Cisco Physical Access Gateway User Guide

 

OL-20932-02

1-7

 

 

 

Page 15
Image 15
Cisco Systems OL-20932-02 manual CAN Bus Connections for Optional Modules, “Connecting a Cisco Reader Module”