Assigning RxPDO to the Sync Manager

To assign RxPDO1 to sync manager 2 PDO assignment set the values below to the following objects:

Index: 0x1C12

Sub index: 0x00

Size: 1

Value: 1

Setting object 0x1C12, sub-index 0 to a value of 1 (as above) indicates that one RxPDO will be assigned to the sync manager 2 assignment.

Index: 0x1C12

Sub index: 0x01

Size: 2

Value: 0x1600

Setting object 0x1C12, sub-index 1 to a value of 0x1600 (as above) maps RxPDO1 to the process data output sync.

Assigning TxPDO to the Sync Manager

To assign TxPDO1 to sync manager 3 PDO assignment set the values below to the following objects:

Index: 0x1C13

Sub index: 0x00

Size: 1

Value: 2

Setting object 0x1C13, sub-index 0 to a value of 2 (as above) indicates that two TxPDO's will be assigned to the sync manager 3 assignment.

Index: 0x1C13

Sub index: 0x01

Size: 2

Value: 0x1A00

Index: 0x1C13

Sub index: 0x02

Size: 2

Value: 0x1A05

Setting object 0x1C13, sub-index 1 to a value of 0x1A00 and sub-index 2 to a value of 0x1A05 (as above) maps TxPDO1 and TxPDO6 to the process data input sync.

Download the configuration to the master.

After downloading the configuration to the master the LED(s) on the front of the SM- EtherCAT should flash, depending on the port(s) connected.

Values written to parameters over RxPDOs should now be viewable using the drive’s keypad so long as the master has put the slave into the Operational state; also, parameter values changed using the drive keypad will be updated on the master.

16

SM-EtherCAT User Guide

www.controltechniques.com

Issue Number: 2

Page 16
Image 16
Emerson 0471-0128-02 manual Assigning RxPDO to the Sync Manager, Assigning TxPDO to the Sync Manager