Table 7.8 CoE state machine transition and events

Transition

Event(s)

Action(s)

0

Automatic transition after power-on or

Drive device self-test and/or self

 

reset application

initialisation shall be performed

 

 

 

1

Automatic transition

Communication shall be activated

2

Shutdown command from control

None

 

device or local signal

 

 

 

 

3

Switch on command received from

Power section shall be switched on if

 

control device or local signal

not already switched on

 

 

 

4

Enable operation command received

Drive function shall be enabled and

 

from control device or local signal

clear all internal set-points

5

Disable operation command received

Drive function shall be disabled

 

from control device or local signal

 

 

 

 

6

Shutdown command received from

The high-power shall be switched-off

 

control device or local signal

immediately, and the motor shall be free

 

 

to rotate if not braked; additional action

 

 

depends on the shutdown option code

7

Quick stop or disable voltage command

None

 

from control device or local signal

 

 

 

 

8

Shutdown command from control

The high-power shall be switched off

 

device or local signal

immediately if possible, and the motor

 

 

shall be free to rotate if not braked

 

 

 

9

Disable voltage command from control

The high-power shall be switched off

 

device or local signal

immediately if possible, and the motor

 

 

shall be free to rotate if not braked

 

 

 

10

Disable voltage or quick stop command

The high-power shall be switched off

 

from control device or local signal

immediately if possible, and the motor

 

 

shall be free to rotate if not braked

 

 

 

11

Quick stop command from control

The quick stop function shall be started

 

device or local signal

 

 

 

 

12

Automatic transition when the quick

The power section shall be switch off

 

stop function is completed and quick

 

 

stop option code 1, 2, 3 or 4 disable

 

 

voltage command received from control

 

 

device (dependant on the quick stop

 

 

option code)

 

 

 

 

13

Fault signal

The configure fault reaction function

 

 

shall be executed

14

Automatic transition

The drive function shall be disabled; the

 

 

high-power may be switched off

 

 

 

15

Fault reset command from control

A reset of the fault condition is carried

 

device or local signal

out, if no fault exists currently on the

 

 

drive device; after leaving the Fault

 

 

state, the Fault reset bit in the

 

 

controlword shall be cleared by the

 

 

control device

 

 

 

16

Enable operation command from control

The drive function shall be enabled

 

device, if the quick stop option code is

 

 

5, 6, 7 or 8

 

32

SM-EtherCAT User Guide

www.controltechniques.com

Issue Number: 2

Page 32
Image 32
Emerson 0471-0128-02 manual CoE state machine transition and events, Transition Events Actions