The time period is checked to ensure that it is an integer multiple of the control loop cycle time. Only linear interpolation is currently supported. This type inserts a delay of one interpolation time period.

The input buffer has a maximum size of 1 data record, and a data record contains one position in profile-defined units. The buffer is a FIFO buffer. Every interpolator time period, a value is read from this buffer. The correct number of data points for a specific interpolation mode are stored internally. When a new position command is loaded in, the oldest position command in the data set is discarded.

7.5vl velocity mode

Velocity mode is supported on Unidrive SP, Digitax ST, Affinity, Mentor MP and Commander SK. It is not, however, supported in regen modes. This mode uses the drive’s speed handling and ramps.

When the attached drive is in either of the closed-loop or servo operating modes the scaled velocity is written to the drive internal speed shortcut. When the attached drive is in an open-loop operating mode the scaled velocity is written to the user preset reference parameter (Pr 1.21). Table 7.36 lists the objects that are supported:

Table 7.36 vl velocity mode supported objects

Index

Name

0x6042

vl_target_velocity

0x6043

vl_velocity_demand

 

 

0x6044

vl_velocity_actual_value

 

 

0x6046

vl_velocity_min_max_amount

0x6047

vl_velocity_min_max

 

 

0x6048

vl_velocity_accleration

 

 

0x6049

vl_velocity_deceleration

0x604A

vl_velocity_quick_stop

 

 

0x604B

vl_setpoint_factor

 

 

0x604C

vl_dimension_factor

7.5.10x6042 vl_target_velocity

This object is used to set the required velocity of the system. It is multiplied by the vl_dimension_factor and the vl_setpoint_factor. The value is given in rpm, If the vl_dimension_factor has the value of 1, otherwise the value is in user units. Positive values indicate forward direction and negative values indicate reverse direction.

Table 7.37 vl_target_velocity

0x6042

vl_target_velocity

 

Access: RW

 

Range: -32768 to +32767

Size: Signed 16

Unit: rpm

 

 

 

 

 

Default:

0

 

 

 

 

 

 

Description:

Used to set the required velocity of the system.

 

Information

Safety

 

Introduction

 

 

Installation

Mechanical

 

 

Installation

Electrical

 

Getting Started

 

Protocols

 

 

support

Drive profile (DSP-402)

features

Advanced

 

Diagnostics

 

 

Reference

Quick

 

 

Terms

Glossary

 

Of

 

Index

 

 

SM-EtherCAT User Guide

41

Issue Number: 2

www.controltechniques.com

Page 41
Image 41
Emerson 0471-0128-02 manual Vl velocity mode, 1 0x6042 vltargetvelocity, vl velocity mode supported objects