MODEL 54eA

SECTION 16.0

 

TROUBLESHOOTING

16.14 SIMULATING TEMPERATURE

16.14.1 General.

The 54eA controller accepts either a Pt100 RTD (for pH, 499ADO, 499ATrDO, 499ACL-01, 499ACL-02, 499ACL-03, and 499AOZ sensors) or a 22k NTC thermistor (for Hx438 and Gx448 DO sensors and most steam-sterilizable DO sensors from other manufacturers). The Pt100 RTD is in a three-wire configuration. See Figure 16-4. The 22k ther- mistor has a two-wire configuration.

16.14.2 Simulating temperature

To simulate the temperature input, wire a decade box to the analyzer or junction box as shown in Figure 16-5.

To check the accuracy of the temperature measurement, set the resistor simulating the RTD to the values indicated in the table and note the temperature readings. The meas- ured temperature might not agree with the value in the table. During sensor calibration an offset might have been applied to make the measured temperature agree with a standard thermometer. The offset is also applied to the simulated resistance. The controller is measuring tempera- ture correctly if the difference between measured tempera- tures equals the difference between the values in the table to within ±0.1°C.

For example, start with a simulated resistance of 103.9 Ω, which corresponds to 10.0°C. Assume the offset from the sensor calibration was -0.3 Ω. Because of the offset, the analyzer calculates temperature using 103.6 Ω. The result is 9.2°C. Now change the resistance to 107.8 Ω, which cor- responds to 20.0°C. The analyzer uses 107.5 Ω to calcu- late the temperature, so the display reads 19.2°C. Because the difference between the displayed temperatures (10.0°C) is the same as the difference between the simu- lated temperatures, the analyzer is working correctly.

FIGURE 16-4. Three-Wire RTD Configuration.

Although only two wires are required to connect the RTD to the analyzer, using a third (and sometimes fourth) wire allows the analyzer to correct for the resistance of the lead wires and for changes in the lead wire resistance with temperature.

FIGURE 16-5. Simulating RTD Inputs.

The figure shows wiring connections for sensors con- taining a Pt 100 RTD. For sensors using a 22k NTC ther- mistor (Hx438 and Gx448 sensors), wire the decade box to terminals 1 and 3 on TB6.

 

Temp. (°C)

Pt 100 (Ω)

22k NTC (kΩ)

 

 

0

100.0

64.88

 

 

10

103.9

41.33

 

 

20

107.8

26.99

 

 

25

109.7

22.00

 

 

30

111.7

18.03

 

 

40

115.5

12.31

 

 

50

119.4

8.565

 

 

60

123.2

6.072

 

 

70

127.1

4.378

 

 

80

130.9

3.208

 

 

85

132.8

2.761

 

 

90

134.7

2.385

 

100

138.5

1.798

 

 

 

 

 

 

105

Page 111
Image 111
Emerson Process Management 53eA instruction manual Simulating Temperature, Simulating temperature, 105