MODEL 54eA

SECTION 5.0

 

SOFTWARE CONFIGURATION

5.14 CONTROLLER MODE PRIORITY

The Model 54eA controller can function in different modes depending on both how it is configured, what process conditions exist, and actions an operator may have made. To reconcile these possible modes, there is a set priority that determines exactly what will happen to the two (2) current outputs and the four (4) alarm relays in the event of multiple modes occurring at the same time. See Table 5-2 below.

Priority is in the following order (from lowest to highest): normal, fault, timer, hold, feed limit, test. Each output or relay acts as if it is only in the state of highest priority.

NOTE

Some of these features may not be in use in the controller.

TABLE 5-2. Controller Mode Priority Chart

 

Condition

Priority

Current

Current

Alarm

Alarm

Alarm

Alarm

 

 

 

Output 1

Output 2

Relay 1

Relay 2

Relay 3

Relay 4

 

 

 

 

 

 

 

 

 

 

 

Normal

1

Normal

Normal

Normal

Normal

Normal

Open

 

 

 

 

 

 

 

 

 

 

 

Fault

2

Default

Default

Default

Default

Default

Closed

 

 

 

 

 

 

 

 

 

 

 

Interval Timer

3

Hold

Hold

Default/

Default/

Default/

Prior

 

 

 

 

 

Normal1

Normal1

Normal1

 

 

 

Hold Mode

4

Hold

Hold

Default

Default

Default

Prior

 

 

 

 

 

 

 

Feed Limit

5

Normal

Normal

Open1

Open1

Open1

Closed

 

 

Simulate tests

6

Test1

Test1

Test1

Test1

Test1

Test1

1Indicates the state IF that item has been configured or selected (i.e. if it is an interval timer or a feed limit timer or it is the one being tested). Unconfigured or unselected items are not affected by that mode.

Condition Definitions:

1.Normal refers to conditions when no other mode is present.

2.Fault means the instrument has diagnosed a fault condition. A fault message is displayed and the red LED is on.

3.Interval Timer means the timer sequence is occurring.

4.Hold Mode occurs when hold is activated by the operator (i.e. during calibration).

5.Feed Limit occurs when a feed limit timer has reached its limit and is turned off after being on for too long.

6.Simulate tests are described in Section 5.4.

Action Definitions:

1.Normal is determined by process conditions or how the item has been configured (Section 5.6)

2.Open is a deenergized alarm relay (alarm off).

3.Default is the setting configured for each item if there is a fault. (Section 5.6)

4.Closed is an energized alarm relay (alarm on).

5.Hold is the setting for the current output configured in Section 5.5 (fixed mA value or the last normal value).

6.Prior is the state the alarm had before that mode occurred.

7.Test is the value input by the operator (mA for current, on or off for a relay).

46

Page 52
Image 52
Emerson Process Management 53eA instruction manual Controller Mode Priority, Condition Definitions, Action Definitions