MODEL 54eA

SECTION 5.0

 

SOFTWARE CONFIGURATION

5.7 CHANGING ALARM PARAMETERS (continued)

FIGURE 5-2. Low Alarm

 

FIGURE 5-3. High Alarm

 

 

 

9.Alarm setup for TPC alarms:

a. Move the cursor to the desired alarm setup and press Enter (F4).

Alarm 1 control

Alarm 1 setup

Alarm 2 control

ExitEnter

Setpoint : 1.000 ppm

Proportional: 100.0%

Integral: 0 sec

ExitEdit

b.Use the é and ê keys to move the cursor to the desired param- eter. Press Edit (F4). Use the arrow keys to change the setting to the desired value and press Save (F4) to store the value

Setpoint: Setpoint is the usually the value to which the process is to be controlled. The alarm will not be on much when the process is at the setpoint value.

Proportional: Proportional is the same as proportional band and is the range over which control is being used. It is the opposite of process gain. Smaller values provide tighter control.

Integral: Integral is the number of seconds over which deviations from the setpoint are integrated to remove continuing offsets. Smaller values provide higher response.

Derivative: Derivative is a form of control that resists all changes in readings. Higher readings increase the derivative function. To prevent process oscillation, use caution in setting the derivative value.

Time period: Time period is the cycle time for TPC control. One cycle consists of an energized (relay on) time and a deenergized (relay off) time.

URV: URV is the deviation from the setpoint that results in the alarm being on all the time.

LRV: LRV is the deviation from the setpoint that results in the alarm being off all the time. The LRV should be set to 0.00.

35

Page 41
Image 41
Emerson Process Management 53eA instruction manual Low Alarm, High Alarm