Installing the Hardware

Connecting the System to the Mains

2

1

Figure 12: Connecting the basic unit to the mains

ÊFirst connect the C19 connector of the power cables to the power supply units of the basic unit (1), and then plug the power plug (2) into the USV, power distribution unit (PDU) or into an external socket.

VCAUTION!

Always connect the power cable to the power supply units first, and then to the mains.

IPlease make sure that each of the power supply units is connected to a different phase. This will provide you with additional phase redundancy for high availability configurations. If one phase has failed, the power supply units connected to the other phases keep active. You can get full phase redundancy with up to three power supply units. With four power supply units, two of them are to be connected to one phase (see also “Related Publications” on page 157).

Phase redundancy is possible in regions, where a single phase provides 200 - 240V; in other regions with lower single phase voltage, two phases must be coupled and complete phase redundancy thus is not possible.

BX600 S3

Operating Manual

47

Page 47
Image 47
Fujitsu BX600 S3 manual Connecting the System to the Mains