HH

MM

SS

##

!

 

 

 

 

ON OFF

MM : SS HH : MM

CP 1

CP 2

C

1 2 3

CP 3

P

 

FIG. 32

Run Mode

Backup Time

In both Cycle and Pressure modes a Backup Time (maximum run time) has been set.

The LED(s) next to all programmed sensors (C/P1, C/P2, C/P3) illuminate.

The display shows time remaining until a fault.

The example shown in FIG. 33 shows 14 min- utes and 33 seconds left until the fault occurs.

If all cycle and/or pressure requirements are met the unit exits the lubrication cycle (Pump ON) and enter the rest cycle (Pump OFF).

HH

MM

SS

##

!

 

 

 

 

ON OFF

MM : SS HH : MM

CP 1

CP 2

C

1 2 3

CP 3

P

 

FIG. 33

Rest Mode (Pump OFF) Controls

In Max models the Rest Mode (Pump OFF) is controlled by machine counts.

If the Machine Count is set to a value greater than 0000 and the Backup Time option is activated, the display will alternate between Machine Counts and Backup Time.

If Machine Count has been set to a value greater than 0000 and the Backup Time option is NOT activated, the display will only show the number of Machines Counts remaining.

332305B

53

Page 53
Image 53
Graco 332305B important safety instructions Backup Time, Rest Mode Pump OFF Controls