Backup Time

HH

MM

SS

##

!

 

 

 

 

ON OFF

MM : SS HH : MM

FIG. 33 CP 1

CP 2

C

1 2 3

CP 3

P

 

FIG. 32

Run Mode

Backup Time

In both Cycle and Pressure modes a Backup Time (maximum run time) has been set.

The LED(s) next to all programmed sensors (C/P1, C/P2, C/P3) illuminate.

The display shows time remaining until a fault.

The example shown in FIG. 33 shows 14 min- utes and 33 seconds left until the fault occurs.

If all cycle and/or pressure requirements are met the unit exits the lubrication cycle (Pump ON) and enter the rest cycle (Pump OFF).

HH

MM

SS

##

!

 

 

 

 

ON OFF

MM : SS HH : MM

Manual background CP 1

CP 2

C

1 2 3

CP 3

P

 

FIG. 33

Rest Mode (Pump OFF) Controls

In Max models the Rest Mode (Pump OFF) is controlled by machine counts.

If the Machine Count is set to a value greater than 0000 and the Backup Time option is activated, the display will alternate between Machine Counts and Backup Time.

If Machine Count has been set to a value greater than 0000 and the Backup Time option is NOT activated, the display will only show the number of Machines Counts remaining.