TWAVeform Subsystem

RANGe

Command

<time_range>

Example

Query

Returned Format

Example

RANGe

:MACHine{12}:TWAVeform:RANGe <time_value>

The RANGe command specifies the full-screen time in the timing waveform menu. It is equivalent to ten times the sec/Div setting on the display. The allowable values for RANGe are from 10 ns to 10 ks.

real number between 10 ns and 10 ks

OUTPUT XXX;":MACHINE1:TWAVEFORM:RANGE 100E9"

:MACHine{12}:TWAVeform:RANGe?

The RANGe query returns the current full-screen time.

[:MACHine{12}:TWAVeform:RANGe] <time_value><NL>

OUTPUT XXX;":MACHINE1:TWAVEFORM:RANGE?"

 

REMove

Command

:MACHine{12}:TWAVeform:REMove

 

The REMove command deletes all waveforms from the display.

 

 

Example

OUTPUT XXX;":MACHINE1:TWAVEFORM:REMOVE"

 

 

13–20

Page 218
Image 218
HP 16554A, 16555D, 16555A manual MACHine12TWAVeformRANGe timevalue, MACHine12TWAVeformRANGe?, MACHine12TWAVeformREMove, 13-20