STRigger (STRace) Subsystem

SEQuence

Query:MACHine{12}:STRigger:RANGe<N>?

The RANGe query returns the range recognizer end point specifications for the range.

Returned Format [:MACHine{12}:STRigger:RANGe<N>] <label_name>,<start_pattern>,<stop_pattern><NL>

Example

OUTPUT XXX;":MACHINE1:STRIGGER:RANGE1?"

 

 

SEQuence

Command:MACHine{12}:STRigger:SEQuence <num_levels>, <trig_level>

<num_levels>

<trig_level>

Example

Query

Returned Format

Example

The SEQuence command redefines the state analyzer trigger sequence. First, it deletes the current sequence. Then it inserts the number of levels specified, with default settings, and assigns the trigger to be at a specified sequence level. The number of levels may be between 2 and 12.

integer from 2 to 12

integer from 1 to (number of existing sequence levels 1)

OUTPUT XXX;":MACHINE1:STRIGGER:SEQUENCE 4,3"

:MACHine{12}:STRigger:SEQuence?

The SEQuence query returns the current sequence specification.

[:MACHine{12}:STRigger:SEQuence] <num_levels>, <trig_level><NL>

OUTPUT XXX;":MACHINE1:STRIGGER:SEQUENCE?"

6–15