IBM System Storage DR550

Version 3.0 ------

17 March 2006

Page 31

 

 

 

 

Site Preparation and Planning

Before you install the IBM System Storage DR550 we recommend that you consider several things to avoid problems during the installation and configuration. The DR550 comes as an almost ready to use system with a complete assembled hardware in a rack (or two) and preconfigured software. Nevertheless we review some topics of importance when planning for the physical installation and configuration of the IBM System Storage DR550 within your environment.

Planning to be done is centered on integrating the rack(s) into the operational IT environment. The racks themselves are already assembled. To integrate the rack(s) into your environment you have to plan or validate the following:

The size of the floor area required by the DR550 rack(s)

Floor load capacity

Space needed for expansion

Service clearance

Check for potential clearance problems along the access route

The power requirements

Multiple 208 volt or 220 volt 30 amp (single phase) power service feeds

￿2 feeds for 5.6, 11.2 and 22.4 TB configurations (both dual engine and single engine configurations)

￿4 feeds for 89.6 TB configurations

Each feed of a pair are recommended to be on a different AC power feed for increased availability

Power cords are shipped with each rack

Climate control is required (Environmental Class A)

Cables and Connectors

RJ-45 to 9-pin converter cable to administer from the front serial port of pSeries (included) – this is an option that only offers limited functions

The network environment

IP addresses

Check for address conflicts before cabling to your network

The table below shows selected factory IP address settings and provides a column to enter the IP addresses to be used later when configuring the DR550. Other IP addresses within DR550 do not need to be changed.

Dual Node Configuration

 

 

IP Description

IP Address from Factory

IP Address in Network

drs_engine1_boot

192.168.1.21

 

drs_engine1_stdby

192.168.2.10

 

drs_engine2_boot

192.168.1.23

 

drs_engine2_stdby

192.168.2.11

 

drs_cluster_svc

192.168.1.22

 

Single Node Configuration

IP Description

drs_engine

IP Address from Factory

IP Address in Network

192.168.1.11

Refer to Configuring the System (P5 520 Servers) section for additional information on IP addresses used for the DR550.

IBM Storage Systems

Copyright © 2006 by International Business Machines Corporation

 

 

Page 31
Image 31
IBM DR550 manual Site Preparation and Planning, IP Description