IBM System Storage DR550 | Version 3.0 | 17 March 2006 | Page 48 |
6.Turn on the branch circuit breaker. Measure for the appropriate voltages between phases. If no voltage is present on the receptacle case or grounded pin, the receptacle is safe to touch.
7.With an appropriate meter, verify that the voltage at the ac outlet is correct.
8.Verify that the grounding impedance is correct by using the ECOS 1020, 1023, B7106, C7106, or an appropriately approved
Cabling AC
The DR550 rack(s) have sets of AC power rails (left and right) traversing vertically in the rear of the rack cabinet. Each rail in a set should be connected to a different AC power feed if that is available. This is to enhance the availability of the rack components. Each power source should be 220V or 200V single phase rated at 30 amps.
For the 5.6 and 11.2 TB configurations, there are two power rails. For the 22.4 and 44.8 TB offering, there are four power rails. For the 89.6 TB offering, there will be eight power rails, 4 per rack. Power cords are shipped with each rack (one per rail) to enable cabling to AC power above or below each rack. Power cords come with NEMA
Each device in the rack is connected to the AC Power Rails. When shipped from the factory each component will have the AC power switch in the OFF position. The SAN Switch (one in the single node configuration or two in the dual node configuration) do not have an AC switch, and thus will be powered up as soon as the rails become energized.
Power on Sequence
The devices in the rack should be powered on in the following sequence:
1.SAN Switch(es) (Before proceeding to step 3, confirm that the SAN Switch(es) have completed their power on sequencing. This is indicated with a green light showing for power.)
2.DS4000 EXP100 Serial ATA drives (0 to 14 devices depending on the disk capacity installed)
3.DS4100 (single device except for 89.6 TB configurations which has two)
4.P5 520 #1 (located at EIA
5.P5 520 #2 (located at EIA
Similarly, should power need to be shut down, the reverse of the power on sequence should be followed (once the applications and operating systems have been shutdown):
1.P5 520 #2 (located at EIA
2.P5 520 #1 (located at EIA
3.DS4100 (single device except for 89.6 TB configurations which has two)
4.DS4000 EXP100 Serial ATA drives (0 to 14 devices depending on the disk capacity installed)
5.SAN Switch(es)
Connect the Drawer and Device Cables
The DR550 rack(s) are preconfigured at the factory with all drawers and device cables installed. To check out the system, refer to the RS/6000 and eServer pSeries Diagnostics Information for Multiple Bus Systems and follow the instructions in the installation checkout procedure.
IBM Storage Systems | Copyright © 2006 by International Business Machines Corporation |
|
|