Connect the positive (+) source cable lugs to the return terminals on the circuit breaker box, which are labeled RTN(+).

Connect the negative (–) source cable lugs to the input terminals on the circuit breaker box, which are labeled –48V.

7.Slide a washer and then screw a nut onto each terminal stud (if the washers and nuts were not installed on the studs, they should be in the accessory box). Using a 7/16-in. nut driver or wrench, tighten the nuts.

CAUTION: Do not substitute a metric nut driver or wrench. A tool that does not fit the nuts exactly can damage them. If a 7/16-in. tool is not available, use pliers or an adjustable wrench.

8.Replace the protective shield on the circuit breaker box and tighten the screws that secure it to the box.

9.Replace the rear lower impeller assembly by lining up the rails with the guides inside the chassis, pushing the impeller straight in, and tightening the thumbscrew at each corner of the impeller cover. For complete instructions, see “Installing the Rear Lower Impeller Assembly” on page 155.

10.Apply voltage from the DC power sources to the power cables so the router receives power.

11.Press the switches on the circuit breaker box to the ON ( ) position.

12.Confirm that the LEDs on the power supply faceplates indicate correct operation: the green CB ON LED lights steadily, the blue OUTPUT OK LED blinks briefly, then lights steadily, and the amber CB OFF LED does not light.

NOTE: After powering off a power supply, wait at least 60 seconds before turning it back on. After powering on a power supply, wait at least 60 seconds before turning it off.

If the router is completely powered down when you power on the power supply, the Routing Engine boots as the power supply completes its startup sequence. If the Routing Engine finishes booting and you need to power down the router again, first issue the CLI request system halt command. For more information, see “Disconnecting Power from the Router” on page 200.

After a power supply is powered on, it can take up to 60 seconds for status indicators—such as LEDs on the power supply, show chassis commands, and messages on the craft interface LCD—to indicate that the power supply is functioning normally. Ignore error indicators that appear during the first 60 seconds.

196 Replacing Power System Components