ground wire or conduit to a solid office (earth) ground. A closed loop ring is recommended for terminating the ground conductor at the ground stud.

Run two wires from the circuit breaker box to a source of 48 VDC. Use appropriate gauge wire to handle up to 90 A.

You must connect only to a DC power source for which the output complies with the safety extra low-voltage (SELV) requirements of UL 1950, CSA C22.2 No. 950-95, EN 60950, and IEC 60950 to a DC-input terminal block.

A DC-powered router that is equipped with a DC terminal block is intended only for installation in a restricted access location. In the United States, a restricted access area is one in accordance with Articles 110-16, 110-17, and 110-18 of the National Electrical Code ANSI/NFPA 70.

NOTE: Primary overcurrent protection is provided by the building circuit breaker. This breaker should protect against excess currents, short circuits, and earth faults in accordance with NEC ANSI/NFPA70.

Ensure that the polarity of the DC input wiring is correct. Under certain conditions, connections with reversed polarity might trip the primary circuit breaker or damage the equipment.

For personal safety, connect the green and yellow wire to safety (earth) ground at both the router and the supply side of the DC wiring.

The marked input voltage of –48 VDC for DC-powered routers is the nominal voltage associated with the battery circuit, and any higher voltages are only to be associated with float voltages for the charging function.

Because the router is a positive ground system, you must connect the positive lead to the terminal labeled RTN(+), the negative lead to the terminal labeled –48V, and the earth ground to the chassis grounding points.

Copper Conductors Warning

WARNING: Use copper conductors only.

Waarschuwing Gebruik alleen koperen geleiders.

Varoitus Käytä vain kuparijohtimia.

Attention Utilisez uniquement des conducteurs en cuivre.

Warnung Verwenden Sie ausschließlich Kupferleiter.

Avvertenza Usate unicamente dei conduttori di rame.

Advarsel Bruk bare kobberledninger.

230 Safety Guidelines and Warnings