INSTALLATION

Return to Section TOC

1.Install the double-pole, double-throw switch between the power company meter and the premises disconnect.

Switch rating must be the same or greater than the cus- tomer’s premises disconnect and service over current protection.

2.Take necessary steps to assure load is limited to the capacity of the Commander by installing a 50 amp, 240 VAC double-pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 50 amperes. Loading above the rated output will reduce output voltage below the allow-

able -10% of rated voltage, which may damage appliances or other motor-driven equipment and may result in overheating of the Commander 500 engine.

3.Install a 50 amp 120/240 VAC plug (NEMA Type 14-50) to the double-pole circuit breaker using No. 6, four-conductor cable of the desired length. (The 50 amp, 120/240 VAC plug is available in the optional K802R plug kit.)

4.Plug this cable into the 50 amp 120/240 volt recep- tacle on the Commander 500 case front.

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

FIGURE A.2 – CONNECTION OF THE COMMANDER 500 TO PREMISES WIRING

 

 

 

240 VOLT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUNDED CONDUCTOR

 

 

 

 

240 Volt

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120 VOLT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60 Hz.

 

COMPANY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-Wire

 

 

120 VOLT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Service

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

METER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEUTRAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BUS

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOUBLE POLE DOUBLE THROW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SWITCH RATING TO BE THE SAME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AS OR GREATER THAN PREMISES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SERVICE OVERCURRENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROTECTION.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PREMISES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISCONNECT AND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SERVICE

 

 

 

 

 

 

 

 

 

 

GROUND

 

 

 

 

 

 

 

 

50AMP

 

OVERCURRENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROTECTION

 

 

 

 

 

 

 

 

240 VOLT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOUBLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50 AMP, 120/240

 

 

 

POLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VOLT PLUG

240 VOLT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BREAKER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEMA TYPE 14-50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

N

50 AMP, 120/240 VOLT

RECEPTACLENOTE: No. 6 COPPER CONDUCTOR CABLE. SEE NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.