Appendix
|
|
|
| Comments |
Fb | Function | WE | Anl | Function block parameters / Range of values (default setting) |
06 | Reverse control | ON | Not | Co4 |
|
|
| 1, 3, 6 | Co4 |
|
|
|
| Function block parameters: |
|
|
|
| Activate priority in case of deviation / 0 to 30 °C (0 °C) |
07 | Time until reverse | ON | Not | Co4 |
| control |
| 1, 2, | Co4 |
|
|
| 3, 6 |
|
08 | Thermal | OFF | Not | Co4 |
| disinfection |
| 1, 3, 6 | Function block parameters: |
|
|
|
| Day of the week /0 = daily, 1 = Monday, 2, …, 7 (3 = |
|
|
|
| Wednesday) |
|
|
|
| Disinfection temperature / 60 to 90 °C (70 °C) |
|
|
|
| Charging boost / 0 to 30 °C (5 °C) |
|
|
|
| Start time / 00:00 to 23:30 h (00:00 h) |
|
|
|
| Stop time / 00:00 to 23:30 h (04:00 h) |
09 | ON | Not | Co4 | |
| ping control |
| 1, 2, | KP (proportional gain) / 0.1 to 50.0 (0.5) |
| for DHW heating |
| 3, 6 | TN (reset time) / 1 to 999 s (200 s) |
|
|
|
| TY (valve transit time) / 15 to 240 s (120 s) |
10 | Storage tank | OFF | Not | Co4 |
| system |
| 1, 3, 6 |
|
11 | Mixing valve | OFF | Not | Co4 |
| always active |
| 1, 3, 6 | losses |
12 | Public holiday and | OFF |
| Co4 |
| vacation data |
| Not | Data for heating circuit / 1 to 3 (1) |
| apply to DHW |
| 1, 3, 6 |
|
| circuit |
|
|
|
13 | Condensate |
|
| Co4 |
| accumulation |
| 7, 8 | Maximum system deviation / 2 to 10 °C (2 °C) |
| control |
|
| For all other systems (Anl) enter under Co5 |
14 | OFF | Not | Co4 | |
| control |
| 1, 3, 6 | Function block parameters: |
| DHW heating |
|
| KP (proportional gain) / 0.1 to 50.0 (0.5) |
|
|
|
| TN (reset time) / 1 to 999 s (200 s) |
|
|
|
| TV |
Fb Function block, WE Default setting |
|
|
100EB 5179 EN