Samson 5179, 5100 operating instructions Co8: Error initialization

Models: 5179 5100

1 142
Download 142 pages 31.78 Kb
Page 105
Image 105
Co8: Error initialization

 

 

 

 

 

 

Appendix

 

Co8: Error initialization

 

 

 

 

 

 

 

 

 

 

Comments

 

 

 

Fb

Function

WE

Anl

Function block parameters / Range of values (default setting)

 

 

00

Dial-up also upon

OFF

All

CO8 -> Fb00 = ON: Dial-up to the building control station

 

 

 

corrected fault

 

 

both when a fault was detected and a fault was corrected

 

 

 

 

 

 

CO8 -> Fb00 = OFF: Dial-up to building control station only

 

 

 

 

 

 

when fault was detected

 

 

01

BE1 in FSr

OFF

All

Co8 -> Fb01 to Fb17 = ON:

 

 

to

to

 

 

Option:

Rising signal edge/make contact

 

 

17

BE 17 in FSr

 

 

 

Negative signal edge/break contact

 

 

 

 

 

 

Note: Can only be changed after entering key number

 

 

 

 

 

 

 

 

 

22

Limit monitoring

OFF

All

Configurable over Modbus

 

 

23

Alarm binary input

OFF

All

Co8 -> Fb23 = ON: Subsequent faults reported in error status

 

 

 

changed

 

 

register (bit D11)

 

Fb Function block, WE Default setting

 

 

 

 

Co9: Modbus and meter bus communication

 

 

 

 

 

 

Comments

 

 

 

FB

Function

WE

Function block parameters / Range of values (default setting)

 

 

00

Modbus

ON

CO9 -> FB00 = ON: Modbus active

 

 

01

Modem

OFF

CO9 -> FB01 = ON: Modem active

 

 

02

Modem dialing

OFF

CO9 -> FB02 = ON: Pulse dialing

 

 

 

mode

 

CO9 -> FB02 = OFF: Tone dialing

 

 

03

Lock dial-up

OFF

CO9 -> FB03 = ON: No dial-up in case of fault

 

 

04

Modbus 16-bit

OFF

CO9 -> Fb04 = ON: 16-bit addressing

 

 

 

addressing

 

CO9 -> Fb04 = OFF: 8-bit addressing

 

 

05

Reserved

 

 

 

 

 

 

06

Text message alarm

OFF

CO9 -> FB06 = ON: Fault alarm sent to mobile phone

 

 

07

Text message

OFF

CO9 -> FB07 = ON: Pulse dialing

 

 

 

dialing mode

 

CO9 -> FB07 = OFF: Tone dialing

 

 

 

 

 

 

 

 

 

 

10

Fax alarm

OFF

CO9 -> FB10 = ON: Alarm sent to fax

 

 

11

Fax dialing mode

OFF

CO9 -> FB11 = ON: Pulse dialing

 

 

 

 

 

CO9 -> FB11 = OFF: Tone dialing

 

 

 

 

 

 

 

 

 

EB 5179 EN 105