Samson 5100, 5179 operating instructions Appendix, Functions

Models: 5179 5100

1 142
Download 142 pages 31.78 Kb
Page 58
Image 58
Manual background

Appendix

Thermal disinfection for preventing legionella infection causes

￿high return flow temperatures during the disinfection cycle (return flow temperature limita- tion suspended),

￿high storage temperatures after thermal disinfection has been concluded,

￿lime scale (possibly), which can have a negative effect on heat exchanger performance.

Note!

This function is not available when a storage tank thermostat is used.

Functions

WE

Configuration

Storage sensor SF1

ON

Co4 -> Fb00 = ON

Thermal disinfection

OFF

Co4 -> Fb08 = ON

 

3

 

Day of the week / 1–7, 1, 2, ..., 7 with

 

 

 

1–7 = every day, 1 = Monday, ..., 7 = Sunday

 

70

°C

Disinfection temperature / 60 to 90 °C

 

5

°C

Charging boost / 0 to 30 °C

 

00:00

Start time / 00:00h to 23:30h (in steps of 30 minutes)

 

04:00

Stop time / 00:00h to 23:30h (in steps of 30 minutes)

58EB 5179 EN

Page 58
Image 58
Samson 5100, 5179 operating instructions Appendix, Functions