Appendix
Thermal disinfection for preventing legionella infection causes
high return flow temperatures during the disinfection cycle (return flow temperature limita- tion suspended),
high storage temperatures after thermal disinfection has been concluded,
lime scale (possibly), which can have a negative effect on heat exchanger performance.
Note!
This function is not available when a storage tank thermostat is used.
Functions | WE | Configuration | |
Storage sensor SF1 | ON | Co4 | |
Thermal disinfection | OFF | Co4 | |
| 3 |
| Day of the week / |
|
|
| |
| 70 | °C | Disinfection temperature / 60 to 90 °C |
| 5 | °C | Charging boost / 0 to 30 °C |
| 00:00 | Start time / 00:00h to 23:30h (in steps of 30 minutes) | |
| 04:00 | Stop time / 00:00h to 23:30h (in steps of 30 minutes) |