Functions of the DHW circuit
Parameters | WE | Parameter level / Range of values |
Day set point | 20 °C | PA1, 2, 3 / 10 to 90 °C |
Night set point | 17 °C | PA1, 2, 3 / 10 to 90 °C |
Sustained temperature | 10 °C | PA1, 2, 3 / 10 to 90 °C |
5.10 Flash adaptation
Direct reactions to deviations in room temperature can be achieved using the function block set- ting: Co1, 2, 3
Flash adaptation counteracts room temperature deviations by increasing or decreasing the flow temperature by up to 30 °C. The shift is displayed under Level in PA1, 2, 3 parameter levels; it cannot be altered. The set point correction over remote room panel is not possible.
Note!
Cooling loads, such as drafts or open windows, affect the control process!
Rooms may be temporarily overheated when the cooling load has been eliminated!
Functions | WE | Configuration |
Room sensor RF1, 2, 3 | OFF | Co1, 2, 3 |
Flash adaptation | OFF | Co1, 2, 3 |
5.11 Adaptation
The controller is capable of automatically adapting the heating characteristic to the building characteristics, provided a gradient characteristic has been set (Co1, 2, 3
Functions | WE | Configuration | |
Room sensor RF1, 2, 3 | OFF | Co1, 2, 3 | |
Outdoor sensor AF1, 2, 3 |
| Co1, 2, 3 | |
Adaptation | OFF | Co1, 2, 3 | |
OFF | Co1, 2, 3 |
48EB 5179 EN