Appendix
Functions | WE | Configuration | |
Room sensor RF1, 2, 3 | OFF | Co1, 2, 3 | |
Room temperature dependent control | OFF | Co1, 2, 3 | |
Parameter optimization | OFF | Co1, 2, 3 | |
Flow sensor OFF when room temperature | OFF | Co1, 2, 3 | |
dependent control is used |
|
|
|
5.13 Pump management
To control the circulation pumps for the heating circuits (UP1 and UP2), reed relay outputs can be used instead of the relay output. Depending on the operating state, the circulation pumps run during the
BA1, BA3: Circulation pump on and off
BA2, BA4: Reduce pump speed
If the circulation pump is to be switched on, the contact of BA1 or BA3 is closed. The binary out- puts BA2 and BA4 can be configured over the function blocks Co1, 2
Co1, 2 |
| BA2, BA4 = OFF outside the | |
Co1, 2 |
| BA2, BA4 = ON outside the | |
|
|
|
|
Function |
| WE | Configuration |
Pump management | OFF | Co1, 2 |
Note!
Refer to the pump manufacturer instructions for the exact terminal assignments of pumps since the terminal assignments vary depending on the pump.
In systems Anl 3, 5, 8 and 10, the pumps of an uncontrolled heating circuit can be switched on and off over an external binary signal. For this purpose, deactivate the Potentiometer input function (Co1 to Co3
50EB 5179 EN