7.8On/off control
The flow temperature can be controlled by an on/off signal. The controlled valve is opened when the flow temperature falls below the set point by T = 0.5 x Hysteresis. When the flow tem- perature exceeds the set point by T = 0.5 x Hysteresis, the control valve is closed. The greater the Hysteresis selected, the lower the switching frequency. The UP lag time parameter indicates the time span which the circulation pump continues to run after the control valve is closed (the pa- rameter only needs to be set for the heating circuits HK1, HK2 and HK3).
By entering Minimum activation time, a burner once switched on remains switched on for the time entered, regardless of how the temperature develops. Likewise, a burner that has been switched off due to the temperatures remains switched off for the time entered in Minimum de- activation time.
The on/off control can be configured separately for the individual heating circuits and for the
Functions | WE | Configuration |
ON | Co1, 2, 3 | |
for heating circuit | 5 °C | Hysteresis / 1 to 30 °C |
| 120 s Minimum activation time / 0 to 600 s | |
| 120 s Minimum deactivation time / 0 to 600 s | |
| 240 s UP lag time / 120 to 1200 s | |
ON | Co5 | |
for | 5 °C | Hysteresis / 1 to 30 °C |
| 120 s Minimum activation time / 0 to 600 s | |
| 120 s Minimum deactivation time / 0 to 600 s |
7.9Continuous-action control
The flow temperature can be controlled using a PID algorithm. The valve receives an analog 0 to 10 V signal issued by the controller. The
The
EB 5179 EN 63