Communication
A system with simultaneous room heating and DHW heating requires maximum energy. A system with a fully charged storage tank which performs only room heating requires less
energy.
A system which suspends room heating during DHW heating requires less energy.
As a result, three different maximum limit values can be specified: Max. limit value to determine the absolute upper limit
Max. limit value for heating for exclusive operation of the room heating Max. limit value for DHW for exclusive operation of the DHW heating
In all systems without DHW heating or without heating circuit, only the Max. limit value for the flow rate or capacity can be set.
Capacity limitation
Parameters | WE | Parameter level / Range of values |
Maximum capacity of the entire system | 50 kW | PA5 / 0.1 to 5999 kW |
Maximum capacity of the DHW heating | 50 kW | PA5 / 0.1 to 5999 kW |
1.0 | PA5 / 0.1 to 10 | |
By selecting “CONST“ additionally |
|
|
Maximum capacity of the heating | 50 kW | PA5 / 0.1 to 5999 kW |
By selecting |
|
|
Outdoor temperature Point 1 | ||
Point 2 | – 5 °C |
|
Point 3 | 5 °C |
|
Point 4 | 15 °C |
|
Maximum limit of capacity, points 1 to 4 | 50 kW | PA5 / 0.1 to 5999 kW |
Flow rate capacity
Parameters | WE | Parameter level / Range of values |
Maximum flow rate of the entire system | 9 m3/h | PA5 / 0.01 to 99.9 m3/h |
Maximum flow rate of the DHW heating | 9 m3/h | PA5 / 0.01 to 99.9 m3/h |
1.0 | PA5 / 0.1 to 10 | |
By selecting “CONST“ additionally |
|
|
Maximum flow rate of the heating | 9 m3/h | PA5 / 0.01 to 99.9 m3/h |
By selecting |
|
|
EB 5179 EN 83