Settings for flow rate limitation
Functions | WE | Configuration | |
Limitation of heat meter (WMZ) | OFF | Co5 | |
Pulse input for flow rate or capacity limitation | OFF | Co5 | |
|
| CONST: | Limitation constant |
|
| Limitation acc. to | |
| 10 |
| |
| Pulse weighting / 0.1 to 10 | ||
|
|
| |
Parameters | WE | Parameter level / Range of values | |
Maximum flow rate of the entire system | 9 m3/h | PA5 / 0.01 to 99.9 m3/h | |
Maximum flow rate of the DHW heating | 9 m3/h | PA5 / 0.01 to 99.9 m3/h | |
1.0 | PA5 / 0.1 to 10 | ||
Select CONST additionally for: |
|
|
|
Maximum flow rate of the heating | 9 m3/h | PA5 / 0.01 to 99.9 m3/h | |
Select |
|
|
|
Outdoor temperature Point 1 | |||
Point 2 | – 5 °C |
|
|
Point 3 | 5 °C |
|
|
Point 4 | 15 °C |
|
|
Maximum flow rate limitation, points 1 to 4 | 9 m3/h | PA5 / 0.01 to 99.9 m3/h |
A second pulse counter can be connected at terminal 29. The pulses entered are stored in the holding registers 40031 (low byte) and 40032 (high byte). The associated duration on the holding registers 40035 (low byte) and 40036 (high byte). First, the low byte counts upwards (0 to 65535). If several pulses arrive, the counting value is formed by multiplying the low byte with the high byte
7.12 Locking manual level
To protect the heating system, this function can be used to lock manual level. When this function has been activated, automatic mode is started when the rotary switch is set to +, – or 0.
Function | WE | Configuration |
Locking manual levels | OFF | Co5 |
66EB 5179 EN