Samson 5100, 5179 operating instructions 1.2Operating modes, Operation

Models: 5179 5100

1 142
Download 142 pages 31.78 Kb
Page 8
Image 8
1.2Operating modes

Operation

The assignment of the control circuits to the mode selector switches depends on the system code number (Anl):

System

 

Mode selector switch

 

(Anl)

Top

Middle

Bottom

1

Heating circuit 1

Heating circuit 2

Pre-control circuit

2

Heating circuit 1

DHW heating

Heating circuit 2

3

Heating circuit 1

Heating circuit 2

Heating circuit 3/Pre-control

 

 

 

circuit

4

Heating circuit 1

DHW heating

Pre-control circuit

5

Heating circuit 1

DHW heating

Heating circuit 2/Pre-control

 

 

 

circuit

6

Heating circuit 1

Heating circuit 2

Heating circuit 3

7

Heating circuit 1

DHW heating

Pre-control circuit

8

Heating circuit 1

DHW heating

Heating circuit 2/Pre-control

 

 

 

circuit

9

Heating circuit 1

DHW heating

Heating circuit 2

10

Heating circuit 1

DHW heating

Heating circuit 2

1.2Operating modes

Day mode (rated operation) Manual background

Regardless of the programmed times-of-use and summer mode, the set points relevant for rated operation are used by the controller.

Night mode (reduced operation)

Regardless of the programmed times-of-use, the set points relevant for reduced operation are used by the controller.

Automatic mode Manual background

During the programmed times-of-use, the controller works in rated operation. Outside these times-of-use, the controller is in reduced operation, unless control operation is deactivated de- pending on the outdoor temperature. The controller switches automatically between both oper- ating modes.

Manual operation+ 0 –

Valves and pumps can be controlled manually.

8EB 5179 EN