11 Electrical connection

!Caution!

For electrical installation, you are required to observe the relevant electrotechnical regulations of the country of use as well as the regulations of the local power suppliers. Make sure all electri- cal work is performed by trained and experienced personnel!

Notes on installing the electrical connections

￿Install the 230 V power supply lines and the signal lines separately! To increase noise immu- nity, observe a minimum distance of 10 cm between the lines. Make sure the minimum dis- tance is also observed when the lines are installed in a cabinet.

￿The lines for digital signals (bus lines) and analog signals (sensor lines, analog outputs) must also be installed separately!

￿In plants with a high electromagnetic noise level, we recommend to use shielded cables for the analog signal lines. Ground the shield at one side, either at the control cabinet inlet or outlet, using the largest possible cross-section. Connect the central grounding point and the PE grounding conductor with a cable 10 mm² using the shortest route.

￿Inductances in the control cabinet, e.g. contactor coils, are to be equipped with suitable in- terference suppressors (RC elements).

￿Control cabinet elements with high field strength, e.g. transformers or frequency converters, should be shielded with separators providing a good ground connection.

Overvoltage protection

￿If signal lines are installed outside buildings or over large distances, make sure appropriate surge or overvoltage protection measures are taken. Such measures are indispensable for bus lines!

￿The shield of signal lines installed outside buildings must have current conducting capacity and must be grounded on both sides.

￿Surge diverters must be installed at the control cabinet inlet.

Connecting the controller

The controller is connected as illustrated in the following wiring diagrams.

If individual inputs for other functions, e.g. for binary inputs, are to be used, they must be deter- mined in the configuration levels (Co1 to Co6).

Open the housing to connect the cables. To connect the feeding cables, make holes in the marked locations at the top, bottom or back of the rear part of the housing and fit suitable cable glands.

90EB 5179 EN

Page 90
Image 90
Samson 5100, 5179 operating instructions Electrical connection

5179, 5100 specifications

The Samson 5179 and 5100 series are renowned for their innovative design and robust performance in various industrial applications. These models are particularly known for their precision control and reliability in managing fluid flow systems.

One of the main features of the Samson 5179 is its advanced control valve technology, which allows for seamless operation across different pressures and flow rates. The valve is designed with a compact and lightweight construction, making it easy to install and maintain. Enhanced sealing mechanisms ensure minimal leakage and increased durability, even under harsh operating conditions.

The Samson 5100, on the other hand, is distinguished by its adaptive control technologies. This model incorporates state-of-the-art automation capabilities, allowing for remote monitoring and adjustments. With its integrated sensors, operators can receive real-time data on pressure, temperature, and flow rates, leading to more informed decision-making.

Both series utilize high-quality materials, ensuring longevity and resistance to corrosion and wear. This characteristic is crucial for applications in industries such as water treatment, chemicals, and pharmaceuticals. The valves are designed to withstand significant pressure differences, enhancing their versatility in various settings.

Another key technology featured in both the 5179 and 5100 series is the user-friendly interface. This interface simplifies configuration and management, enabling operators to program performance parameters quickly. The intuitive design minimizes the learning curve, allowing teams to leverage the system’s capabilities effectively.

Additionally, both models are compliant with international standards, making them suitable for global applications. This compliance not only ensures safety but also enhances market acceptance across various regions.

Energy efficiency is another important characteristic of the Samson 5179 and 5100 series. With optimized flow dynamics, these valves minimize energy consumption while maintaining high performance, making them a sustainable choice for companies aiming to reduce their environmental footprint.

In summary, the Samson 5179 and 5100 series stand out due to their innovative features, robust construction, and advanced technologies. With a focus on precision, reliability, and efficiency, these models are poised to meet the evolving demands of modern industrial applications. Their adaptability and user-friendly interfaces make them ideal for operators seeking streamlined operations and enhanced productivity.