Samson 5100, 5179 operating instructions Electrical connection

Models: 5179 5100

1 142
Download 142 pages 31.78 Kb
Page 90
Image 90
11 Electrical connection

11 Electrical connection

!Caution!

For electrical installation, you are required to observe the relevant electrotechnical regulations of the country of use as well as the regulations of the local power suppliers. Make sure all electri- cal work is performed by trained and experienced personnel!

Notes on installing the electrical connections

￿Install the 230 V power supply lines and the signal lines separately! To increase noise immu- nity, observe a minimum distance of 10 cm between the lines. Make sure the minimum dis- tance is also observed when the lines are installed in a cabinet.

￿The lines for digital signals (bus lines) and analog signals (sensor lines, analog outputs) must also be installed separately!

￿In plants with a high electromagnetic noise level, we recommend to use shielded cables for the analog signal lines. Ground the shield at one side, either at the control cabinet inlet or outlet, using the largest possible cross-section. Connect the central grounding point and the PE grounding conductor with a cable 10 mm² using the shortest route.

￿Inductances in the control cabinet, e.g. contactor coils, are to be equipped with suitable in- terference suppressors (RC elements).

￿Control cabinet elements with high field strength, e.g. transformers or frequency converters, should be shielded with separators providing a good ground connection.

Overvoltage protection

￿If signal lines are installed outside buildings or over large distances, make sure appropriate surge or overvoltage protection measures are taken. Such measures are indispensable for bus lines!

￿The shield of signal lines installed outside buildings must have current conducting capacity and must be grounded on both sides.

￿Surge diverters must be installed at the control cabinet inlet.

Connecting the controller

The controller is connected as illustrated in the following wiring diagrams.

If individual inputs for other functions, e.g. for binary inputs, are to be used, they must be deter- mined in the configuration levels (Co1 to Co6).

Open the housing to connect the cables. To connect the feeding cables, make holes in the marked locations at the top, bottom or back of the rear part of the housing and fit suitable cable glands.

90EB 5179 EN

Page 90
Image 90
Samson 5100, 5179 operating instructions Electrical connection