Samson 5100, 5179 operating instructions Entering public holidays, Operation

Models: 5179 5100

1 142
Download 142 pages 31.78 Kb
Page 16
Image 16
1.6.2 Entering public holidays

Operation

1.6.2 Entering public holidays

On public holidays, the times-of-use specified for Sunday apply. A maximum of 20 public holi- days may be entered.

Parameters

WE

Level / Range of values

Public holidays f. heating circuit 1

PA1 / 01.01 to 31.12

Public holidays f. heating circuit 2

PA2 / 01.01 to 31.12

Public holidays f. heating circuit 3

PA3 / 01.01 to 31.12

 

 

 

Note!

The programmed public holidays and vacations of any heating circuit (HK1, HK2 or HK3) ap- ply with the setting Co4 -> Fb12 = ON , select 1, 2 or 3 also for the DHW heating.

Proceed as follows:

Switch to configuration and parameter level.

 

 

 

 

 

 

 

Display: PA1

 

 

 

 

 

 

 

Select parameter level.

 

 

 

 

 

 

 

Open parameter level.

 

 

 

 

 

 

 

Select datapoint for public holidays.

0

1 2

3 4

5 6

7 8

9

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display shows:

 

 

 

 

 

 

 

Open data point for public holidays.

 

 

 

 

 

 

 

If applicable, select – – – .

 

 

 

 

 

 

 

Activate editing mode for public holiday.

 

 

 

 

 

 

 

blinks.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Edit public holiday

Confirm public holiday.

To enter additional public holidays, re-select – – – – (between 31.12 and 01.01) and repeat the steps in the fields highlighted in gray.

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background Exit the parameter level.

Return to the operating level.

16EB 5179 EN