Appendix

 

 

 

 

Comments

 

 

Fb

Function

WE

Anl

Function block parameters / Range of values (default settings)

09

RK switched off

OFF

All

Co1, 2, 3 -> Fb09 = ON: UP still runs until 1 x TY.

 

when switch at

 

 

The flow sensor is no longer be read.

 

MAN-CLOSED

 

 

 

 

 

10

4-point character-

OFF

Not

Co1, 2, 3 -> Fb10 = ON: 4-point characteristic

 

istic

 

3, 5,

Co1, 2, 3 -> Fb10 = OFF: Gradient characteristic

 

 

 

8, 10

 

 

 

11

Summer mode

ON

All

Co1, 2, 3 -> Fb11 = ON: Function block parameters:

 

 

 

 

Start summer mode / 01.01 to 31.12 (01.05)

 

 

 

 

End summer mode/

01.01 to 31.12 (30.09)

 

 

 

 

Outdoor temp. limit for summer mode / 0 to 30 °C (18 °C)

12

Potentiometer input

OFF

All

Co1, 2, 3 -> Fb12 = ON: Valve position feedback

 

Release HK

 

 

(0 to 1000 Ω), 1000 Ω additional resistor required

 

 

 

 

Co1, 2, 3 -> Fb12 = OFF: RK released with binary signal;

 

 

 

 

Option

FrG-E:

Released over bin. signal (potentiometer)

 

 

 

 

 

FrG-A:

Released over time schedule

 

 

 

 

With FrG-A:RLG:

Configuration acc. to input

 

 

 

 

 

FREE:

Input freely available

13

Pump

OFF

All

Co1, 2 -> Fb13 = ON: BA 2, 4 OFF outside time-of-use

 

management

 

 

Co1, 2 -> Fb13 = OFF: BA 2, 4 ON outside time-of-use

14

Continuous-action

OFF

All

Co1, 2, 3 -> Fb14 = ON: Continuous-action control 0 to 10 V

 

control for heating

 

 

Function block parameters:

 

circuit

 

 

KP (proportional gain) / 0.1 to 50.0 (0.5)

 

 

 

 

TN (reset time) / 1 to 999 s (200 s)

 

 

 

 

TV (derivative-action time) / 0 to 999 s (0 s)

15

Three-step control

ON

All

Co1, 2, 3 -> Fb15 = ON: Three-step control;

 

for heating circuit

 

 

Function block parameters:

 

 

 

 

KP (proportional gain) / 0.1 to 50.0 (0.5)

 

 

 

 

TN (reset time) / 1 to 999 s (200 s)

 

 

 

 

TY (valve transit time) / 15 to 240 s (120 s)

 

 

 

 

UP lag time / 120 to 1200 s (240 s)

 

 

 

 

Co1, 2, 3 -> Fb15 = OFF: On/off control

 

 

 

 

Function block parameters:

 

 

 

 

Hysteresis / 1 to 30 °C (5 °C)

 

 

 

 

Min. activation time / 0 to 600 s (120 s)

 

 

 

 

Min. deactivation time / 0 to 600 s (120 s)

 

 

 

 

UP lag time / 120 to 1200 s (240 s)

16

Parameter

OFF

6, 9

Co1, 2, 3 -> Fb16 = ON: Automatic parameter optimization

 

optimization

 

 

(KP, TN, TV)

 

 

98EB 5179 EN