Appendix
|
|
|
| Comments |
|
|
Fb | Function | WE | Anl | Function block parameters / Range of values (default settings) | ||
09 | RK switched off | OFF | All | Co1, 2, 3 | ||
| when switch at |
|
| The flow sensor is no longer be read. | ||
|
|
|
|
|
| |
10 | OFF | Not | Co1, 2, 3 | |||
| istic |
| 3, 5, | Co1, 2, 3 | ||
|
|
| 8, 10 |
|
|
|
11 | Summer mode | ON | All | Co1, 2, 3 | ||
|
|
|
| Start summer mode / 01.01 to 31.12 (01.05) | ||
|
|
|
| End summer mode/ | 01.01 to 31.12 (30.09) | |
|
|
|
| Outdoor temp. limit for summer mode / 0 to 30 °C (18 °C) | ||
12 | Potentiometer input | OFF | All | Co1, 2, 3 | ||
| Release HK |
|
| (0 to 1000 Ω), 1000 Ω additional resistor required | ||
|
|
|
| Co1, 2, 3 | ||
|
|
|
| Option | Released over bin. signal (potentiometer) | |
|
|
|
|
| Released over time schedule | |
|
|
|
| With | Configuration acc. to input | |
|
|
|
|
| FREE: | Input freely available |
13 | Pump | OFF | All | Co1, 2 | ||
| management |
|
| Co1, 2 | ||
14 | OFF | All | Co1, 2, 3 | |||
| control for heating |
|
| Function block parameters: | ||
| circuit |
|
| KP (proportional gain) / 0.1 to 50.0 (0.5) | ||
|
|
|
| TN (reset time) / 1 to 999 s (200 s) | ||
|
|
|
| TV | ||
15 | ON | All | Co1, 2, 3 | |||
| for heating circuit |
|
| Function block parameters: | ||
|
|
|
| KP (proportional gain) / 0.1 to 50.0 (0.5) | ||
|
|
|
| TN (reset time) / 1 to 999 s (200 s) | ||
|
|
|
| TY (valve transit time) / 15 to 240 s (120 s) | ||
|
|
|
| UP lag time / 120 to 1200 s (240 s) | ||
|
|
|
| Co1, 2, 3 | ||
|
|
|
| Function block parameters: | ||
|
|
|
| Hysteresis / 1 to 30 °C (5 °C) | ||
|
|
|
| Min. activation time / 0 to 600 s (120 s) | ||
|
|
|
| Min. deactivation time / 0 to 600 s (120 s) | ||
|
|
|
| UP lag time / 120 to 1200 s (240 s) | ||
16 | Parameter | OFF | 6, 9 | Co1, 2, 3 | ||
| optimization |
|
| (KP, TN, TV) |
|
|
98EB 5179 EN