7.5Condensate accumulation control
Activate the Condensate accumulation control function to start up condensate accumulation plants, in particular to avoid problematic excess temperatures. The controller response to set point deviations which cause the primary valve to open is attenuated. The controller response to set point deviations which cause the control valve to close remains unaffected.
In systems Anl 6 and 9, the limitation applies to all control valves; in all other systems, it applies to the control valve with the highest flow temperature set point.
In systems with DHW heating on the primary side (Anl 7 and 8), the Condensate accumulation control function must configured separately under Co4.
Functions | WE | Configuration |
Condensate accumulation control | OFF | Co5 |
| 2 °C | Maximum system deviation / 2 to 10 °C |
Condensate accumulation control |
| Co4 |
(Anl 7 and 8) | 2 °C | Maximum system deviation / 2 to 10 °C |
|
|
|
Note!
The condensate accumulation control function can only be activated when no on/off control has been configured, i.e. Co5
7.6Compensating for time delays
The controller regulates the control circuit with the highest flow set point with the secondary flow sensor. If the sensor is placed on the secondary side directly downstream of the heat exchanger and the setting Co5
Functions | WE | Configuration |
Flow sensor, secondary VFsek | ON | Co5 |
Compensation of time delays | OFF | Co5 |
|
|
|
EB 5179 EN 61