Samson 5100, 5179 operating instructions 9.5LON communication, Communication

Models: 5179 5100

1 142
Download 142 pages 31.78 Kb
Page 84
Image 84
9.5LON communication

Communication

Outdoor temperature Point 1

–15 °C

PA5 /–30 to 90 °C

Point 2

– 5

°C

 

Point 3

5

°C

 

Point 4

15

°C

 

Maximum limit of flow rate, points 1 to 4

9 m3/h

PA5 / 0.01 to 99.9 m3/h

9.5LON communication

Note!

The following section only applies to devices with LON interface and CO7 -> Fb00 = ON. On connecting LONMARK devices, CO7 -> Fb00 = OFF needs to be configured.

Each controller is assigned a LON station address, which needs to be set in the PA7 parameter level. A station address in a subnet must be unique. Each controller type is assigned its own subnet. This means that identical LON station addresses can be assigned for different controller types, e.g. 5174 and 5179, as they belong to different subnets. A maximum of 59 participants consisting of TROVIS 5171, 5174, 5177 and 5179 can be connected together.

Controller type

Subnet

Station address

TROVIS 5171

1

1 to 20

TROVIS 5174

4

1 to 20

TROVIS 5177

7

1 to 20

TROVIS 5179

9

1 to 20

The controller sends its inputs and outputs as well as pulse counters and their pulse duration over the LON network to a TROVIS 5171 Programmable Logic Controller.

The pulse inputs are sent after four minutes; the sensor temperatures when the temperature has changed by at least 1 °C or after four minutes at the latest. The analog inputs and outputs are sent when the signal level changes by 0.5 V. The binary inputs and outputs are sent after every change or after four minutes at the latest.

In the InF7 level, all other TROVIS 5100 network participants are listed together with controller type and LON address (e.g. “74-01“). A communication fault exists when the display blinks.

Function

WE

Configuration

LON active

OFF

Co7 -> Fb00 = ON

84EB 5179 EN

Page 84
Image 84
Samson 5100, 5179 operating instructions 9.5LON communication, Communication