Appendix
5.14 Releasing the heating circuit
The release of the heating circuit in automatic mode is a default setting after the time schedule has been programmed. In addition, it is possible to release the heating circuit over the corre- sponding potentiometer inputs. When no signal exists at these inputs and the slide switch of the heating circuit is positioned to automatic mode ( ), the heating circuit is in
Function | WE | Configuration |
Potentiometer input for release of HK | OFF | Co1, 2, 3 |
|
| |
|
| |
|
| with |
|
| FREE: Input freely available |
5.15 Position feedback in pre-control circuit
A potentiometer for position feedback (series resistor: 1000 Ω) can be connected at terminal 27 instead of a potentiometer to shift the set point over the room sensor.
The actual position of the valve in the
The valve position is displayed in % of the travel in the operating level at the end of the control circuit data for the
Function | WE | Configuration |
Potentiometer in | OFF | Co5 |
|
|
|
Note!
The potentiometer input HK2 is not available when Co5
EB 5179 EN 51