Samson 5100, 5179 the heating systems have been calibrated, System-widefunctions

Models: 5179 5100

1 142
Download 142 pages 31.78 Kb
Page 60
Image 60
–the heating systems have been calibrated.

System-wide functions

Function

WE

Configuration

Return flow sensor RüF1, 2, 3

OFF

Co1, 2, 3

-> Fb01 = ON

 

1.0

Limitation factor / 0 to 25.5

 

 

 

Parameters

WE

Parameter level / Range of values

Max. return flow temperature

65 °C

PA1, 2, 3

/ 20 to 90 °C

 

 

 

 

Min. return flow temperature

20 °C

PA1, 2, 3

/ 20 to 90 °C

In systems with a DHW in a secondary circuit, the control during DHW heating uses the Return flow limitation temperature for DHW parameter (systems Anl 2, 4, 5 and 10). In the transition time or in summer mode, the heating circuit can be operated with a lower return flow tempera- ture while at the same time performing proper storage tank charging.

The Return flow limitation temperature for DHW parameter can also be active in systems Anl 4, 5, 7, 8, 9 and 10 at a separate return flow sensor. The separate sensor RüFTW (return flow sen- sor for DHW) must in this case be installed in the return flow of the DHW circuit.

Note!

In system Anl 2 , the sensor RüFprim is installed in the return flow of the primary circuit. In this case, the Return flow sensor, primary function must be activated (Co5 -> Fb01 = ON).

Function

WE

Configuration

Return flow sensor in DHW circuit

OFF

Co4 -> Fb02 = ON

 

1.0

Limitation factor / 0 to 25.5

 

 

 

Parameter

WE

Parameter level / Range of values

Return flow limitation temperature for DHW

45 °C

PA4 / 20 to 90 °C

 

 

 

Note!

To ensure that the preset return flow temperature limit can be met, make sure that

the heating characteristic is not adjusted to ascend too steeply,

the speed of the circulation pumps is not set too high,

the heating systems have been calibrated.