Connecting the sensors
Cables with a minimum
Connecting the actuators
Connect cables with at least 1.5 mm² suitable for damp locations to the terminals of the control- ler output. The direction of travel needs to be checked at
Set mode switch to (+). Valves must open. Set slide switch to
Connecting the pumps
Connect all cables with at least 1.5 mm² to the terminals of the controller as illustrated in the corre- sponding connection diagram
Wiring plan legend (page 92 to 96):
AA | Analog output 0 to 10 V | VFS | Flow sensor in storage tank |
AE | Analog input 0 to 10 V | VFT | Flow sensor in heat exchanger |
BA | Binary output | GND Ground | |
BA1 | UP HK1 ON/OFF | GWx Limit alarm to terminal x | |
BA2 | UP HK1 Speed reduced | GWy Limit alarm to terminal y | |
BA3 | UP HK2 ON/OFF | ZB | Meter bus |
BA4 | UP HK2 Speed reduced | HK | Heating circuit |
BE/V Binary input for flow rate | FW | District heating circuit | |
AF | Outdoor sensor | TW | DHW circuit |
FG | Potentiometer (terminal 3 at Type 5244) | SLP | Storage tank charging pump |
RF | Room sensor (terminal 1 at Type 5244) | TLP | Heat exchanger charging pump |
RüF | Return flow sensor | UP | Circulation pump |
SF | Storage tank sensor | ZP | Circulation pump |
| (1: Storage tank ON; 2: Storage tank OFF) |
|
|
STh | Storage tank thermostat | Option Type 5244 or | |
VF | Flow sensor | (Terminal base of room panel is illustrated) | |
|
|
EB 5179 EN 91