Appendix

Display

Parameter designation

Range of values (default settings)

 

 

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

˚C

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

˚C

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

˚C

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

START

˚C

Level of the heating characteristic, return flow

–30 to 30 °C (0 °C)

Characteristic is shifted parallel.

Max. return flow temperature

20 to 90 °C (65 °C)

Only with Co5 -> Fb01 = ON, select: steig

Min. return flow temperature

20 to 90 °C (20 °C)

Only with Co5 -> Fb01 = ON, select: steig

Control according to fixed set point:

Min. return flow temperature = Max. return flow temperature

OT activation value in rated operation

–30 to 50 °C (–15 °C)

The heating continues to run and is not set back outside the time-of-use when the outdoor temperature is below the OT limit.

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Manual backgroundManual background ˚C

STOP

OT deactivation value in reduced operation

–10 to 50 °C (10 °C)

The heating is switched off outside the time-of-use when the out- door temperature is above the OT limit.

110EB 5179 EN