8.3Temperature monitoring

Operational faults

8.3Temperature monitoring

The flow temperature and the room temperature can be monitored for any deviations. This func- tion is activated in Co5 -> Fb20. The controller issues an alarm when:

￿the flow temperature deviates from its set point by more than 10 °C for more than 30 minutes

￿the room temperature falls below its set point by 2 °C for more than 30 minutes ￿the return flow temperature limitation is active for more than 30 minutes.

When one of these conditions occurs, the bit for the associated sensor is set in holding regis- ter 857. A set bit in holding register HR 857 causes the bit 4 to be set in the error status register FSR2 (HR 61) and in the error archive register 2 (HR 63) and the error counter (HR 64) is incre- mented.

Function

WE

Configuration

Temperature monitoring

OFF

Co5 -> Fb20 = ON

Holding register 857 (

 

 

appears on the right-hand side of the set bit number)

 

Number = Bit number in HR

0 1 2 3 4 5 6 7 8 9 10 11 12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VFprim:

Measured value (set point + 10 °C)

RüFprim:

Limitation active

 

(actual return flow blinks in InF5)

VF1:

Meas. value > (set point +10 °C)

RüF1:

Limitation active

RF1:

Meas. value < (set point – 2 °C)

VF2:

Meas. value > (set point + 10 °C)

RüF2:

Limitation active

RF2:

Meas. value < (set point – 2 °C)

VF3:

Meas. value > (set point + 10 °C)

RüF3:

Limitation active

RF3:

Meas. value < (set point – 2 °C)

VFTW:

Meas. value > (set point + 10 °C)

RüFTW:

Limitation active

 

(actual return flow blinks in InF4)