| Appendix |
|
Co5: General functions and |
|
| |||||||
|
|
|
|
| Comments |
|
| ||
| Fb | Function | WE | Anl | Function block parameters / Range of values (default setting) |
| |||
| 00 | Flow sensor | ON | All | Co5 |
| |||
|
| secondary VFsek |
|
| In systems Anl 6 and 9 not possible with Co5 |
| |||
| 01 | Return flow sensor | ON | Not | Co5 |
| |||
|
| primary |
| 6, 9 | Option | steig | Limitation acc. to gradient characteristic |
| |
|
|
|
|
|
|
| Limitation acc. to |
| |
|
|
|
|
| Note: Can only be changed after entering key number |
| |||
| 02 | Reserved | OFF | All |
|
|
|
|
|
| 03 | OFF | 3, 5, 8, | Co5 |
| ||||
|
| characteristic |
| 10 | Co5 |
| |||
|
|
|
|
| Setting applies for all heating circuits. |
| |||
| 04 | Delayed | OFF | All | Co4 |
| |||
|
| outdoor tempera- |
|
| Ab |
| When outdoor temperature drops |
| |
|
| ture adaptation |
|
| AufAb | When outdoor temperature drops or rises |
| ||
|
|
|
|
| Function block parameter: |
| |||
|
|
|
|
| Delay / 1 to 6 °C/h (3 °C/h) |
| |||
| 05 | Summer | ON | All | Co4 |
| |||
|
| time/winter time |
|
| Automatic summer time/winter time changeover |
| |||
|
| changeover |
|
|
|
|
|
|
|
| 06 | Compensation of | OFF | 1, 2, | Co5 |
| |||
|
| time delays |
| 4, 7, |
|
|
|
|
|
|
|
|
| 10 |
|
|
|
|
|
| 07 | Condensate | OFF | All | Co5 |
| |||
|
| accumulation |
|
| Function block parameter: |
| |||
|
| control |
|
| Maximum system deviation / 2 to 10 °C (2 °C) |
| |||
| 08 | Limitation of WMZ | OFF | Not | Co5 |
| |||
|
|
|
| 6, 9 | Select limitation, depending on Co9 |
| |||
|
|
|
|
| No limitation |
| |||
|
|
|
|
| U: | Flow rate limitation |
| ||
|
|
|
|
| P: | Capacity limitation |
| ||
|
|
|
|
|
| ||||
|
|
|
|
| when “U“, “P“ or |
| |||
|
|
|
|
| CONST: | Limitation constant |
| ||
|
|
|
|
|
| Limitation acc. to |
| ||
|
|
|
|
|
|
| dependent on outdoor temperature |
| |
|
|
|
|
| Note: Can only be changed after entering key number |
|
EB 5179 EN 101