Samson 5100, 5179 operating instructions Appendix, PA4: DHW heating

Models: 5179 5100

1 142
Download 142 pages 31.78 Kb
Page 112
Image 112
PA4: DHW heating

Appendix

Display

Parameter designation

Range of values (default settings)

 

 

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Copy times-of-use of HK2 for HK3

 

 

Only in systems Anl 3, 6

 

 

 

PA4: DHW heating

 

 

Display

Parameter designation

Range of values (default settings)

 

 

 

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

˚C

DHW demand ON

20 to 90 °C (40 °C)

Systems with a storage sensor SF1 Co4 -> Fb02 = ON , Fb02 = OFF

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

˚C

Hysteresis

0 to 30 °C (5 °C)

DHW demand ON

20 to 90 °C (40 °C)

Systems with two storage sensors SF1 and SF2 Co4 -> Fb02 = ON , Fb02 = ON

112EB 5179 EN

Page 112
Image 112
Samson 5100, 5179 operating instructions Appendix, PA4: DHW heating