Appendix
12 Appendix
12.1 Function block lists
Co1 to Co3: Heating circuit 1 to 3
|
|
|
| Comments |
Fb | Function | WE | Anl | Function block parameters / Range of values (default settings) |
00 | Room sensor | OFF | All | Co1, 2, 3 |
| RF1, 2, 3 |
|
| In systems Anl 3, 5 and 8 only for optimization and display |
01 | Return flow sensor | OFF | All | Co1, 2, 3 |
| RüF1, 2, 3 |
|
| Function block parameters: |
|
|
|
| Limitation factor / 0 to 25.5 (1.0) |
|
|
|
| In system Anl 6 only after entering key number. |
02 | Outdoor sensor | * | All | Co1, 2, 3 |
| AF1, 2, 3 |
|
| Option: Sensor |
| * HK1 = ON |
|
| Lon1 |
| HK2 = OFF |
|
| Lon2 |
| HK3 = OFF |
|
| In HK1 it can only be deactivated when all heating circuits are |
|
|
|
| configured as room |
|
|
|
| door temperature is then set to the fictive value of 3 °C. |
03 | Reserved |
|
|
|
04 | Reserved |
|
|
|
05 | Optimization | OFF | All | Co1, 2, 3 |
|
|
|
| Option: 1 Activation according to outdoor temperature; |
|
|
|
| |
|
|
|
| 2 Activation according to outdoor temperature; |
|
|
|
| |
|
|
|
| 3 Activation and deactivation acc. to room sensor |
|
|
|
| * Function block parameters: |
|
|
|
| Advance heating time / 0 to 360 min (120 min) |
|
|
|
| Option 2 and 3 only with Co1, 2, 3 |
06 | Room temperature- | OFF | 6, 9 | Co1, 2, 3 |
| dependent control |
|
| trol active |
07 | Adaptation | OFF | Not | Co1, 2, 3 |
|
|
| 3, 5, 8 | Co1, 2, 3 |
08 | Flash adaptation | OFF | Not 3, | Co1, 2, 3 |
|
|
| 5, 8 | only with Co1, 2, 3 |
EB 5179 EN 97