12.5 Technical data

Appendix

12.5 Technical data

Inputs

 

Sensor inputs

Max. 17 configurable inputs for temperature sensors

 

Pt 100, Pt 1000, Ni 200, Ni 1000 und PTC, NTC, 0–10 V, 0/4–20 mA

 

or binary alarms (heating/DHW circuit)

 

5 flow temperature sensors,

 

2 outdoor temperature sensors,

 

2 return flow temperature sensors,

 

2 room temperature sensors,

 

2 storage tank temperature sensors

Binary inputs

Storage tank thermostat

Other inputs

Pulse counter input for flow rate or capacity limitation

 

Inputs for valve position feedback, remote operation to correct the

 

room temperature and to select the operating mode

Outputs

 

Analog output

3 outputs

Control signal y

0 to 10 V (load > 4.7 kΩ)

 

Three-step signal: 230 V~, 2 A

 

On/off signal: 230 V~, 2 A

 

 

Binary outputs

5 outputs to control pumps, 230 V~, 3 A

 

4 outputs for alarms max. 50 V DC, 100 mA

Operating voltage

230 V, 48 to 62 Hz, 8 VA

Interface

RS-232 for connection to a modem, interface for meter bus

 

LON (free topology)

Ambient temperature

0 to 40 °C

Storage temperature

–20 to 60 °C

Degree of protection

IP 40 according to IEC 529

Class of protection

II according to VDE 0106

 

 

Degree of contamination

2 according to VDE 0110

Overvoltage category

II according to VDE 0110

Humidity rating

F according to VDE 40040

Noise immunity

According to EN 61000-6-1

Noise emission

According to EN 61000-6-3

Weight

Approx. 0.6 kg

 

 