1.6Setting the times-of-use

Operation

1.6Setting the times-of-use

Two times-of-use can be set for each day of the week. If just one time-of-use is required, the start and stop times of the second time-of-use must be programmed to identical times. The time schedules for the three heating circuits, DHW heating and the circulation pump can be read over Modbus. Pump circuits are treated as mixer circuits.

Time schedule

Parameter level

 

 

 

Icon

Heating circuit 1 to 3

PA1 to PA3

 

 

 

 

 

 

 

 

 

 

 

 

DHW heating

PA4

 

 

 

 

Circulation pump

PA4

 

 

 

 

Parameters

WE*

Range of values

Period/day

1–7

1–7, 1, 2, 3, 4, 5, 6, 7 with 1–7 = every day,

 

 

1 = Monday, 2 = Tuesday, ..., 7 = Sunday

Start first time-of-use

07:00

0:00 to 24:00h; in steps of 30 minutes

Stop first time-of-use

12:00

0:00 to 24:00h; in steps of 30 minutes

Start second time-of-use

12:00

0:00 to 24:00h; in steps of 30 minutes

Stop second time-of-use

22:00

0:00 to 24:00h; in steps of 30 minutes

* Default settings (WE) valid for heating circuits 1 to 3

Proceed as follows:

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Switch to configuration and parameter level. Display: PA1

Select parameter level.

Open parameter level.

Manual background0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Select datapoint for times-of-use.

EB 5179 EN 13