Appendix
Parameter | WE | Parameter level / Range of values |
Day set point | 20 °C | PA1, 2, 3 / 10 to 90 °C |
5.12 Room temperature-dependent control
In systems Anl 6 and 9, the Room
The outdoor sensors are not required for the room control function, but are still required for the Frost protection function. The outdoor sensor AF1 can also be deactivated if all the control cir- cuits are configured as room control circuits.
Activation of the room control function causes the control parameters to be automatically set to the following settings:
TN (reset time) = 1617 s, TV
With the aid of Parameter optimization (Co1, 2, 3
In room control circuits, the heating circuit pump is switched on during the advance heating phase.
Note!
A fictive flow set point is reported to master controller in case there is a demand for an exter- nally required signal when the room control function is active. This set point is calculated from the characteristic and outdoor temperature and adapted to the actual demand over adaptation and flash adaptation.
The fictive flow set point has no effect on mixer circuits and blinks on the display. Just the third type of optimization is permitted when the room control is active.
!Note! The frost protection cannot function without an outdoor sensor.
EB 5179 EN 49