A heat meter with pulse output connected at input Vmax (terminal 30) can be used either to limit the system flow rate (parameter code: U) or the system capacity (parameter code: P). The pulse weighting of the heat meter (WMZ) and the type of limitation selected must be entered. The dis- played value corresponds to the unit l/pulse or kWh/pulse.
When the pulse rate reaches the current maximum limit, the flow set point of the control circuit RK1 is reduced. How strongly the controller responds is determined by the
Example to determine the limit value:
If a capacity of 30 kW is to be limited, the following limit value must be set for a heat meter with an output of one pulse per
P = | 30 kW |
| = 30 pulse / h |
| |
1 KWh / pulse |
| ||||
Settings for capacity limitation |
|
|
|
| |
|
|
| |||
Functions | WE | Configuration | |||
Limitation of heat meter (WMZ) | OFF | Co5 | |||
Pulse input for flow rate or capacity limitation | OFF | Co5 | |||
|
|
|
| CONST: | Limitation constant |
|
|
|
| Limitation acc. to | |
|
| 10 |
| ||
|
| Pulse weighting / 0.1 to 10 | |||
|
|
| |||
Parameters | WE | Parameter level / Range of values | |||
Maximum capacity of the entire system | 50 kW | PA5 / 0.1 to 5999 kW | |||
Maximum capacity of the DHW heating | 50 kW | PA5 / 0.1 to 5999 kW | |||
1.0 | PA5 / 0.1 to 10 | ||||
Select CONST additionally for: |
|
|
|
| |
Maximum capacity of the heating | 50 kW | PA5 / 0.1 to 5999 kW | |||
Select |
|
|
|
| |
Outdoor temperature Point 1 | |||||
Point 2 | – 5 °C |
|
| ||
Point 3 |
| 5 °C |
|
| |
Point 4 | 15 °C |
|
| ||
Maximum capacity limitation, points 1 to 4 | 50 kW | PA5 / 0.1 to 5999 kW |
EB 5179 EN 65