12.2 Parameter list

Appendix

12.2 Parameter list

PA1 to PA3: Heating circuits HK1 to HK3

Display

Parameter designation

Range of values (default settings)

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Gradient of the heating characteristic, flow

0.4 to 3.2 (1.8)

Level of the heating characteristic, flow

–30 to 30 °C (0 °C)

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

4-point characteristic

Press key to adjust the following parameters: outdoor temperature,

flow temperature,

return flow temperature and set-back difference.

4-point characteristic

Point 1: Outdoor temperature

Outdoor temperatures of the points 2, 3, 4 are marked by squares below the numbers 2, 3, 4.

–30 to 90 °C

(point 1 = –15 °C, point 2 = –5 °C, point 3 = 5 °C, point 4 = 15 °C)

EB 5179 EN 107

Page 107
Image 107
Samson 5179, 5100 operating instructions Parameter list, Appendix, PA1 to PA3: Heating circuits HK1 to HK3