10 - 4 REGULATOR

The compressed air (primary side) in the air tank is governed to preset pressures by regulators before the air pressure is sent to the cylinders. Check set pressure every 2 months.

Remove Lid Left from the Mechanism Base (refer to 11-1) to have the Regulator Unit appear, and check the pressure with the Pressure Gauge attached to each Regulator. If the pressure within the Compressor is insufficient, the Regulator's Pressure Gauge will not indicate the correct value. When checking, first turn the Main SW on and wait until the Compressor operation stops. Pressure settings given at the time of shipment are shown in FIG. 10. 4.

6.0kgf/cm2

(0.60MPa)

3.0kgf/cm2

(0.30MPa)

HIGH LOW

HIGH LOW

PULL DOWN

PULL DOWN

FIG. 10. 4

If the actual pressure is different from the set pressure, adjust it as follows:

Before proceeding the work, be sure to turn the Main SW off. However, if the pressure within the Compressor is insufficient, adjustments can not be performed correctly. First, turn the Main SW on, and after the Compressor operation stops, turn the SW off, and then proceed the work.

Method of adjustment

1Pull down the Adjustment Knob of the Regulator until a click is heard.

2Turn the Adjustment Knob to make adjustment to the preset pressure.

3When the correct setting is established, push up the adjustment knob until a click is heard.

4After the setting is finished, play game and check the regulator's pressure gauge once again.

61www.seuservice.com

Page 70
Image 70
Sega WaveRunner owner manual 10 4 Regulator