Send documentation comments to mdsfeedback-doc@cisco.com.
AppendixB Technical Specifications
Supported Power Supply Plugs
B-6
Cisco MDS 9216 Switch Hardware Installation Guide
78-16165-01
Supported Power Supply Plugs
A separate power cord is provided for each power supply. The power cords have
an IEC C15 connector on the end that plugs into the switch.
Note Only the power cords provided with the switch are supported.
Figure B-1 shows the supported power supply plugs for the CiscoMDS 9216
Switch.
TableB-6 Sample Calculation for Power and Heat Dissipation
Module Type /
Product Number Qty
Power
Required
(Watts)
Heat
Dissipation
(BTU/hr.)
Input Current
90 VAC
(amps)
120 VAC
(amps)
180 VAC
(amps)
240 VAC
(amps)
Cisco MDS 9216
chassis with fan module
DS-C9216-K9
1 38 164 0.53 0.40 0.27 0.20
Fixed supervisor
module (16-port FC
module, 1Gbps/2Gbps)
1 220 940 3.05 2.29 1.53 1.15
32-port FC module,
1Gbps/2Gbps
DS-X9032
1 200 855 2.78 2.08 1.39 1.04
Total 458 1959 6.36 4.77 3.19 2.39