Chapter 2 Installing the Cisco MDS 9216 Switch

Pre-Installation

Send documentation comments to mdsfeedback-doc@cisco.com.

If mounting the switch in a cabinet that has solid front and back doors:

The distance between the side edge of the chassis and the side of the cabinet should be at least 2.5 inches (6.4 cm). No sizeable flow obstructions should be in the way of the chassis side air intake or exhaust vents.

The cabinet depth should be 36 - 42 inches (91.4 - 106.7 cm) to allow adequate airflow. If cable management brackets are used, the front mounting rails of the cabinet should be offset from the front door by 6 inches (15.2 cm) minimum.

The distance between the outside face of the front mounting rail and the outside face of the back mounting rail should be 24 - 34 inches (61.0 - 86.4 cm) to allow for rear bracket installation, with a recommended distance of 25 inches (63.5 cm).

A fan tray in the top of the cabinet to exhaust the heated air, with a minimum of 500 CFM of airflow exiting the top of the cabinet.

Bottom to top air cooling scheme with the bottom of the cabinet open for air intake. There should be a minimum of 150 square inches (968 square cm) of open area at the floor air intake of the cabinet. The lowest piece of equipment should be installed a minimum of 1.75 inches (4.4 cm) above the floor openings to prevent blocking the floor intake.

For all mounting options, the chassis should be adequately grounded. Grounding the chassis is recommended. If the switch is not mounted in a grounded rack, we recommend connecting both the system ground on the chassis and the power supply ground to an earth ground.

Use the following screw torques:

Captive screws: 4 in-lbs

M3 screws: 4 in-lbs

M4 screws: 12in-lbs

10-32 screws: 20in-lbs

12-24 screws: 30in-lbs

 

 

Cisco MDS 9216 Switch Hardware Installation Guide

 

 

 

 

 

 

78-16165-01

 

 

2-5

 

 

 