Cisco Systems manual Table A-4 Cisco XR 12406 Router Environmental Specifications

Models: XR 12406

1 228
Download 228 pages 4.1 Kb
Page 202
Image 202

Appendix A Cisco XR 12406 Router Technical Specifications and Warnings

Specifications

Table A-4

Cisco XR 12406 Router Environmental Specifications

 

 

 

 

Description

 

Value

 

 

 

 

Temperature

 

32° to 104°F (0° to 40°C) operating

 

 

–4° to 149°F (–20° to 65°C) non-operating

 

 

 

Humidity

 

10 to 90% noncondensing operating

 

 

5 to 95% noncondensing non-operating

 

 

 

Altitude

 

0 to 10,000 ft. (0 to 3,050 m) operating

 

 

0 to 30,000 ft. (0 to 9,144 m) non-operating

 

 

 

Heat dissipation

5,828

Btu/hr maximum (AC original series)

 

 

8,871

Btu/hr maximum (AC enhanced series)

 

 

5,562

Btu/hr maximum (DC original series)

 

 

8,871

Btu/hr maximum (DC enhanced series)

 

 

 

Cooling

 

Facing the router, right-side-to-back cooling

 

 

 

Shock

 

5 to 500 Hz, 0.5g1 (0.1 oct/min2) operating

 

 

5 to 100 Hz, 1g (0.1 oct/min) non-operating

 

 

100 to 500 Hz, 15g (0.2 oct/min)

 

 

500 to 1,000 Hz, 1.5g (0.2 oct/min)

 

 

 

 

1.g = Gravity

2.oct/min = Octave per minute

Caution Exhaust from other equipment vented directly into the Cisco XR 12406 Router air inlet may cause overheating. Install the router so that it is protected from a direct flow of hot air from other equipment.

 

Cisco XR 12406 Router Installation Guide

A-4

OL-13831-01

Page 202
Image 202
Cisco Systems manual Table A-4 Cisco XR 12406 Router Environmental Specifications