Chapter 5 Maintaining the Router

Removing and Replacing a DC PDU

Input OK (green)—Indicates that the power supply is operating normally, and the source DC input voltage is within the nominal operating range of -40.5VDC to -75VDC. This indicator should light when the power supply switch is set to the On (1) position.

If the Input OK indicator remains off after checking all of the power sources, replace the power supply with a spare.

If the spare power supply does not work, replace the PDU.

Miswire (amber)—Indicates the input wiring is incorrect at the PDU power connection block.

Correct wiring to the DC power connector block (see Figure 5-24).

Removing and Replacing a DC PDU

The DC PDU does not support online insertion and removal (OIR) and cannot be replaced while the system is operating. You must power off the router before replacing the PDU.

Caution To remove and replace the DC PDU, the system must be powered off. Notify the network administrator and other appropriate personnel that all routing traffic stops while the PDU is replaced.

 

 

Cisco XR 12406 Router Installation Guide

 

 

 

 

 

 

OL-13831-01

 

 

5-31

 

 

 

Page 171
Image 171
Cisco Systems XR 12406 manual Removing and Replacing a DC PDU